Quadratum S12 G2 Surface is a sealed luminaire suitable for use in subsurface rail environments.
- Designed in accordance with fire precautions for subsurface rail stations (Section 12).
- Complies with London Underground subsurface standard S1085 utilising low smoke, zero halogen cables and control gear.
- Impact resistance rating: IK08 (5 joules of energy).
- Ingress protection rating: IP65.
- Designed to prevent the ingress of dust and moisture.
- Surface mounted installation.
- Zinc coated steel body finished in white polyester powdercoat.
- Frosted glass diffuser.
- Integral electronic control gear with fused terminal block.
For more information on our S12 subsurface rail luminaires
Technical Information
L609.4mm x W609.4mm x H100mm | ||||||
LED, Frosted Glass Diffuser | Temp | Load | Lum/lm | Efficacy | CRI | Weight |
D936-G2-2000N-TW-ST | 4000 K | 17.4W | 2110 lm | 122 lm/W | CRI>80 | 12.3kg |
D936-G2-3000N-TW-ST | 4000 K | 24.6W | 3018 lm | 123 lm/W | CRI>80 | 12.3kg |
D936-G2-4000N-TW-ST | 4000 K | 31.7W | 3997 lm | 126 lm/W | CRI>80 | 12.3kg |
D936-G2-5000N-TW-ST | 4000 K | 41.5W | 5019 lm | 121 lm/W | CRI>80 | 12.3kg |
Emergency Output | 4000 K | – | 560 lm | – | – | – |
Quadratum S12 G2 Surface contains a light source of energy efficiency class C.
Quadratum S12 G2 Surface LED Lifetime L80B10>72,000h at 25oC ambient.
Quadratum S12 G2 Surface Driver Lifetime up to 100,000h at 25oC ambient.
Fittting Options
Integral 3 hour duration emergency | add suffix -E3 |
Self test 3 hour duration emergency | add suffix -ES |
DALI 3 hour duration emergency | add suffix -ED |
DALI dimming/monitoring | add suffix -DA |
Switch dimming | add suffix -DI |
Warm white LEDs (3000K) | replace N with W |